How to specify a pressure transmitter

A pressure transmitter that is wrong for the process can drift, fail early or give misleading readings. This guide sets out the information needed to specify one properly.

Last reviewed November 4, 2026

Start with the measurement

First decide what pressure is being measured. Gauge pressure is referenced to atmosphere; absolute pressure is referenced to a vacuum; differential pressure is the difference between two process points, used for filter monitoring, level and flow. Sealed-gauge types are sometimes used where atmospheric venting is undesirable. Then define the normal operating pressure, the minimum and maximum, and the range you want the output to cover.

Choose a range so that normal operation sits comfortably within it, not at the extremes. Also state any pressure spikes, water hammer or vacuum the instrument may see, so that overpressure limits can be checked.

Process conditions and wetted materials

List the medium, its temperature range and anything that affects materials: chlorides, acids, abrasive solids, viscosity, crystallising or sticky fluids. The diaphragm and process connection must be compatible with the medium, and seals must suit both medium and temperature. Viscous, dirty or hygienic duties may call for a flush diaphragm or a diaphragm seal. Steam service normally needs a siphon or impulse line to keep the sensor away from high temperature, and pulsating pumps may need a snubber.

Accuracy, and what it actually means

Accuracy figures are not all calculated the same way. Some are stated as a percentage of span, some of full scale, and some include only part of the error budget. Ask what the figure includes — non-linearity, hysteresis and repeatability — and look separately at temperature effects and long-term stability, which often dominate in real installations. Specify the accuracy you need for the application rather than the best available, because tighter accuracy usually costs more and needs more careful installation and calibration.

Output, power and communication

State the signal the control system expects. A two-wire 4–20 mA loop is the common industrial choice; voltage outputs and digital protocols such as HART or Modbus are also used. Give the supply voltage available, load or cable length if known, and whether local display or configuration is needed.

Installation and environment

Give the process connection (thread type and size, or flange), mounting position, electrical connection, ambient temperature range, and the ingress protection required for the location. If the transmitter will sit in a hazardous area, state the area classification so that only suitably certified instruments are considered. Note also whether isolation and vent valves or a manifold are needed; a gauge root valve or manifold makes removal and calibration safer.

Documents and checking

Say which documents you need, such as a calibration certificate or material certificates for wetted parts. Plan how the instrument will be checked in service, and whether a calibrator or reference gauge is available on site. A complete specification avoids the most common problems: wrong range, incompatible materials and a signal that does not match the control system.

Common mistakes to avoid

The most frequent problems are a range chosen far wider than the process needs, which wastes resolution; wetted materials chosen by habit rather than checked against the medium; transmitters on steam lines mounted without a siphon or impulse line; and outputs that do not match the input card in the control system. Checking each of these before ordering is quicker than correcting them after installation.

General guidance for preparing an enquiry. It is not a substitute for a qualified engineering review of your application.

Checklist for your enquiry

Share what you know. Anything you are unsure of can be marked “not known” — our engineers will help confirm it.

  • Measurand
  • Pressure type
  • Range
  • Overpressure
  • Medium
  • Process temperature
  • Wetted material
  • Process connection
  • Accuracy
  • Signal
  • Supply voltage
  • Electrical connection
  • Ingress protection
  • Hazardous area
  • Calibration certificate

Have a requirement?

Send what you know and an engineer will help with the rest.

Related products and solutions

Product family

Pressure transmitters

Pressure transmitters measure gauge, absolute or differential pressure and send a proportional electrical signal to a controller or display. They are used…

Pressure, level, temperature
Product family

Pressure transducers

Pressure transducers are compact sensing elements that convert gas or liquid pressure into an electrical signal for building into machines, instruments and…

Pressure, level, temperature
Product family

Digital pressure gauges

Digital pressure gauges show pressure on an electronic display instead of a dial, for servicing, calibration checks and test work. Battery and…

Pressure, level, temperature
Product family

Pressure calibrators and manometers

Pressure calibrators and digital manometers are used to check mechanical and electronic pressure instruments against a reference. Calibration kits combine a pressure…

Pressure, level, temperature
Product family

Hydrostatic level transmitters

Hydrostatic level transmitters are submersible pressure sensors that measure liquid level from the pressure of the column above them. They are used…

Pressure, level, temperature
Product family

Differential-pressure flow sensors

Differential-pressure flow sensors infer flow from the pressure drop across a primary element such as an orifice plate, venturi or pitot tube.…

Flow measurement
Product family

Condensate pots and air headers

Condensate pots for steam and vapour impulse lines and air headers for distributing instrument air, in carbon steel, mild steel and stainless…

Piping and hydraulic connections
Product family

Needle valves

Instrument needle valves for fine flow regulation and isolation on gauge, transmitter, sampling and process lines, machined from bar stock or forgings…

Valves and manifolds
Product family

Gauge root valves

Gauge root valves for the first isolation point between a process tapping and its impulse line, gauge or transmitter, in bar-stock construction…

Valves and manifolds
Product family

Instrumentation valve manifolds

Instrument valve manifolds in 2-valve, 3-valve and 5-valve configurations for isolating, equalising, venting and calibrating pressure and differential pressure transmitters and gauges…

Valves and manifolds
Product family

Instrument hook-up assemblies

Instrument hook-up assemblies that connect a process tapping to a pressure gauge or transmitter, combining root valves, tubing, fittings, manifolds and, where…

Valves and manifolds

Frequently asked questions

What is the difference between a pressure transmitter and a transducer?

The terms overlap, but a transmitter usually conditions the sensor signal into a standard industrial output, such as 4–20 mA, for sending over distance to a control system. A transducer often gives a lower-level or voltage output. Specify by the output your system needs rather than by the name.

Do I need a manifold or root valve with a pressure transmitter?

It is good practice. A root valve or valve manifold lets the instrument be isolated, vented and calibrated without shutting down the line. Differential-pressure transmitters normally use a manifold with an equalising valve. Choose valves rated for the line pressure, temperature and medium.