Instrumentation & measurement
Pressure-independent control valves
Pressure-independent control valves (PICVs) combine a differential pressure regulator and a control valve in one body, so flow through a coil or circuit stays at its set value as system pressure changes. They are mainly used in HVAC water systems.
Overview
In a variable-flow water system, pressure at each branch rises and falls as other valves open and close, so a conventional control valve delivers more or less flow than intended. A PICV includes a built-in regulator that holds a constant pressure difference across its control element, so the flow at any actuator position depends only on that position. This simplifies balancing, because maximum flow is set on the valve itself, and gives steadier temperature control at fan-coil units, air-handling units and other terminal units.
Selecting the right PICV
Size a PICV by the design flow of the coil or circuit rather than by pipe size, and check that this flow sits within the valve's adjustable range. Confirm the minimum differential pressure the valve needs to regulate, the maximum pump head, the actuator type and control signal, the power supply and the end connections. Water quality and glycol content also matter.
Information that speeds up a quotation
Share what you know. Anything you are unsure of can be marked “not known” — our engineers will help confirm it.
- Fluid
- Control range
- Voltage
- Pressure
- Port size
- Signal
- Certification
Need a datasheet?
Add this family to your enquiry list and mention the variant — we will send the relevant technical documents.
Pneumatic and process controls
Related and alternative families
Proportional flow controllers
Proportional flow controllers regulate flow continuously in response to a control signal, opening a valve by the amount needed rather than simply…
Solenoid valves
Solenoid valves are electrically operated valves that open or close a line, or switch flow between ports, when a coil is energised.…
Pneumatic cylinders
Pneumatic cylinders convert compressed-air pressure into linear motion for pushing, pulling, clamping and positioning in automated machines. The range covers compact single-acting…
Air-line filters and regulators
Compressed-air line filters remove water, oil, dirt and odour from compressed air to protect valves, cylinders, instruments and other equipment downstream of…
Air dryers and filter elements
Compressed-air dryers remove water vapour from compressed air to prevent condensation in lines and equipment, and replaceable filter elements keep line filters…
Speed controllers and actuators
Valve actuators automate ball, butterfly and plug valves and dampers using air or electric power, and hydraulic speed controllers smooth and regulate…
Frequently asked questions
What information do you need to quote PICVs?
Provide a valve schedule with the design flow for each coil or circuit, pipe sizes, the system's maximum differential pressure, the control signal (on/off, floating or modulating) and actuator supply voltage, the end connection, and the fluid with any glycol content. Mention whether test points or isolation are wanted, so the valve options can be matched to the schedule.
Does a PICV remove the need for balancing valves?
A PICV sets and limits its own maximum flow, so separate balancing valves on that branch are often not needed, and commissioning is mainly a matter of setting each valve. Whether other balancing devices can be left out depends on the overall system design, which should be confirmed by the HVAC designer for the project.